ANSI/ISA-TR96.05.01 is informative and does not contain anymandatory requirements.
ANSI/ISA-TR96.05.01 is limited to automated valves normallyoperating in either a full open or full closed position.
The boundary of the automated valve includes the following:
a) Limit switches and other monitoring devices
b) Air regulation and filtration system
c) Actuated valves whose fail position is specified asspring-return fail closed, spring-return fail open, or doubleacting
d) Valve body specified to meet the functional requirements forits application
ANSI/ISA-TR96.05.01 does not address automated valves used forregulatory control applications.
Guidance is provided on the following:
a) Identifying when partial stroke testing may be useful
b) Various criteria to consider when selecting the partialstroke method, e.g., automated versus manual test execution,spurious trip potential, and on-line maintainability
c) The advantages and disadvantages of three basic types ofpartial stroke test methods: mechanical limiting, positioners, andsolenoid operated valves
d) The use of diagnostic coverage factors in the performancecalculations for an automated block valve being partial stroketested periodically